Near Miss - Dropped birdcage from heater treater

Country: USA - North America

Location: ONSHORE

Incident Date: 7 January 2019   Time: ---

Type of Activity: Maintenance, inspection, testing

Cause: Dropped objects

Function: Production


What happened?:

The Production Operator was attempting to light the burner on the heater treater utilizing the Profire control system. After several failed attempts, an audible flash was observed. This sudden flash lifted the bird cage off the top of the exhaust stack. The bird cage weighs 19 pounds and fell an estimated 29 feet to the ground. It landed approximately 4 feet from the Operator.

What Went Wrong?:

  • The burner was not lighting as normal and took several attempts which allowed gas to accumulate.
  • The current SOP for lighting the burner was generalized/ lacking prescription.
  • The bird cage was not physically restrained to the burner.

Corrective Actions and Recommendations:

  1. Provide immediate guidance for safe operations of BMS while long term improvements are made.
  2. Review the Lease Operator training program module on Heater Treaters and close any gaps identified within the SOPs.
  3. Review training for all operators (employees & contractors) for BMS, explaining this incident.
  4. Review engineering design of BMS: recommended specs (restart times, disable manual mode, passcodes), review other safety devices within the system (permissible starting, purge fire tube, etc.), use of heat tracer installed for all fuel lines
  5. Review the process to secure all bird cages on heater treaters.

Figure 1: Bird cage

images

Figure 2: Bird cage (rain cap) - placing

images


Safety Alert number: 319
IOGP Safety Alerts http://safetyzone.iogp.org/

Disclaimer

Whilst every effort has been made to ensure the accuracy of the information contained in this publication, neither the IOGP nor any of its members past present or future warrants its accuracy or will, regardless of its or their negligence, assume liability for any foreseeable or unforeseeable use made thereof, which liability is hereby excluded. Consequently, such use is at the recipient's own risk on the basis that any use by the recipient constitutes agreement to the terms of this disclaimer. The recipient is obliged to inform any subsequent recipient of such terms.
This document may provide guidance supplemental to the requirements of local legislation. Nothing herein, however, is intended to replace, amend, supersede or otherwise depart from such requirements. In the event of any conflict or contradiction between the provisions of this document and local legislation, applicable laws shall prevail.


IOGP
City Tower, 40 Basinghall Street
Level 14
London, London EC2V 5DE
United Kingdom