What would you find during a ‘hazard hunt’ focused on explosion-proof electrical boxes on your rig? In this incident, a damaged explosion-proof box near the shale shakers became the ignition source for gas breaking out of the non-aqueous mud returns,
and the resulting explosion ignited a fire in the mud itself.
High gas was present around the shakers because a bottoms-up after a bit trip was not circulated through the choke manifold and the mud-gas separator to manage the increased gas contained in the mud. Instead, the system relied on gas breaking out in the
flowline and venting to the mud-gas separator. Is your system plumbed so that it can accommodate occasional higher gas concentrations? Are your crews trained to anticipate such situations and to respond properly?
IOGP Wells Expert Committee/Well Control Incident Subcommittee believes that this incident description contains sufficient lessons to be shared with the industry. We further encourage the recipients of this mail to share it further within their organization.
Unconventional oil-producer. Drilling assembly was pulled out of hole, new drilling assembly tripped back to bottom. Production hole drilling operations resumed, no bottoms-up circulated prior to recommencing drilling operations. While drilling ahead, shortly
before bottoms-up, gas units (recorded at possom bellies) showed increasing trend in tandem with increased flow (recorded at flowline via flo-sho device) and flare actuated (dedicated flare line from MGS). The on-tour driller heard a "hiss and loud pop" between
shakers and substructure area, then observed smoke in the vicinity of the rig floor / substructure / drawworks; then a fire was observed at the shakers. The driller ceased rotation of the drilling assembly and turned the mud pumps off, departed the rig floor
and secured the well by functioning the annular preventer closed from the accumulator unit. All on-duty personnel were mustered. Pipe rams were functioned closed from the accumulator unit to further secure the well, the rig was powered down, fuel sources isolated.
Fire-fighting services were called to the location to extinguish the fire.
|