Uncontrolled release of wellbore gas at surface during slickline plug retrieval operations resulting in well control incident.


Slickline operation. While POOH FBN plug retrieval tool, observed a gas leak on lubricator stuffing box. Attempted to increase the pressure of the stuffing box, no success. Activated BOP upper blind rams, observed it closed but gas still leaking. Attempted to close lower rams, no success. Observed a leak in the hydraulic connection. Cut cable and shut well in by closing Xmas tree master valve.

What Went Wrong?:

  • Failure of stuffing box preparation (wrong packing elements installed)
  • Failure in PCE preparation (equalizing port left open - bypassing the rams)
  • Failure of hydraulic connection - not tested
  • Decision to secure the well by shut in at the Xmas tree and cut the cable delayed due to lack of emergency procedure and clear responsibilities established

Corrective Actions and Recommendations:

  • Pressure Control Equipment is valid only if Certified / Inspected / Maintained / Tested
  • Responsibilities and Emergency Responses procedures to be defined before the operations
  • Well Intervention supervisor to verify PCE status and Referential compliance


safety alert number: 310
IOGP Well Control Incident Lesson Sharing http://safetyzone.iogp.org/

Disclaimer

Whilst every effort has been made to ensure the accuracy of the information contained in this publication, neither the IOGP nor any of its members past present or future warrants its accuracy or will, regardless of its or their negligence, assume liability for any foreseeable or unforeseeable use made thereof, which liability is hereby excluded. Consequently, such use is at the recipient's own risk on the basis that any use by the recipient constitutes agreement to the terms of this disclaimer. The recipient is obliged to inform any subsequent recipient of such terms.
This document may provide guidance supplemental to the requirements of local legislation. Nothing herein, however, is intended to replace, amend, supersede or otherwise depart from such requirements. In the event of any conflict or contradiction between the provisions of this document and local legislation, applicable laws shall prevail.

IOGP
City Tower, 40 Basinghall Street
Level 14
London, London EC2V 5DE
United Kingdom